代做ENGM029 Power System Analysis Lab Sheet _ Lab 1代做Python编程

- 首页 >> Web

ENGM029

Power System Analysis

Lab Sheet Lab 1

Before your Start

•   Ensure you read the instruction document ‘DIgSILENT PowerFactory Modelling Instruction’ and DIgSILENT tutorial documents ‘DIgSILENT Tutorial_Introduction’, ‘DIgSILENT Tutorial_Project’, ‘DIgSILENT Tutorial_LoadFlow’ in the ELE page;

•   DIgSILENT PowerFactory provides Student Licence (PF4S); you are encouraged to make direct contact with DIgSILENT to acquire one licence so you can install in your own computer and can access to and practice the simulation study remotely.

Requirements on Report

•   A report needs to be produced to answer each question in the lab sheet.

•   Assessment: The lab report has a total of 100 marks. The lab report counts for 10% of your final mark.

•   The report should be written in a concise manner to both summarising and discussing the results.

•   The report  should be  submitted as PDF file online through ELE2 system by noon,  1st December 2023.

•  Avoid any form. of plagiarism.

•   Format to be used for the results:

Voltage in p.u.:

3 decimal places

(e.g., 0.965 p.u.)

Voltage in kV:

1 decimal place

(e.g., 132.5 kV)

Power in MW/MVA:

1 decimal place

(e.g., 200.7 MW)

1. Objective

The first Power System Analysis lab aims to enhance your knowledge and skills in power system modelling and power flow calculation and analysis. At the end of the lab session, you should be able to build simple power network model, including generator, transformer, transmission line and load, and carry out power flow simulation and analyse by explaining indicative parameters such as active power, reactive power, bus voltage magnitude and phase angle.

2. Introduction

In this Lab Session, you will learn how to simulate a small power transmission network and  how to perform. power flow calculation in a powerful modern power system simulation software, DIgSILENT PowerFactory. By this simulation exercise, you will learn the underload and  overload effects over a long transmission distance on the system operational performance, mitigation method to stablise the bus voltage, and the efficient Newton-Raphson approach and its application in simulation calculation.

3.  Problem 1 _ Power Flow Problem [50 marks]

Preparation

Open the project file ‘Power System Analysis_Lab  1_P1.pfd’. Ensure the library contains generator type G1, tower type L6, conductor types 1Z×275 kV_ASCR Zebra 400 mm2  and 4Z×275 kV_ASCR Zebra 400 mm2  (300×300).

Problem formation:

A load centre is supplied by hydro-generator (11 kV terminal voltage) through a 11/275 kV step-up transformer, a 200 km long double-circuit transmission line operating at 275 kV, and a 275/33 kV step-down transformer. The configuration of the transmission system is given in the Figure Q1. The load level varies from 40 MW to 340 MW.

Figure Q1

The parameters of the components are given in the following tables:

Transmission Line

Table 1 Double-circuit Transmission Line Parameter

Line length

200 km

Tower Type

L6

Transposition

Perfect (or none)

Conductor Type

4Zx275kV_ASCR Zebra 400mm2 (300x300)

Earth Conductor Type

1Zx275 kV_ASCR Zebra 400mm2

Note: tower, conductor and earth conductor types are included in the library in the project file. Transformer

Table 2. Transformer Parameters

Voltage Ratio

Connection

Power Rating

Short-circuit  impedance %

Load loss kW

No

load

current %

No Load loss kW

Step-up

transformer

T1

1-2

11/275

Yd11

180

MVA

15

450

0.5

60

Step-down transformer

T2

3-4

275/33

YNd11

200

MVA

16

500

0.8

80

Bus

Table 3 Bus Voltage

Bus Number

Voltage Rating kV

Bus 1

11

Bus 2

275

Bus 3

275

Bus 4

33

Generator

Table 4. Generator Parameters

Bus type

G1

Rated Apparent Power

400 MVA

Rated Voltage

11 kV

Rated Power Factor

1.

Note: generator type is included in the library in the project file

Question 1.1: Network conditions with loads at unity power factor [15 marks]

•    Run power flow calculation for loads of 40, 80, 120, 160, 240 and 280 MW

•    Record the active and reactive powers as well as voltage magnitudes and phases of

the generator bus and load bus. Present your recordings in the form. of table/figure in your report;     [10 marks]

•    Discuss your findings;                                                                                       [5 marks]

•    Note:

o To change the setting of active power for the load, go into the power flow’ tab in the load model;

o To run a power flow calculation, click on the ‘Load Flow Calculation’ button

Question 1.2: Network conditions with loads at 0.9 inductive power factor [15 marks]

•    Change the load power factor to 0.9 inductive by introducing appropriate MVAr values

•    Run power flow calculation for loads of 40, 80, 120 and 160 MW. And record the

new active and reactive powers as well as voltage magnitudes and phases of the

generator bus and load bus. Present your recordings in the form. of table/figure in your report;          [10 marks]

•    Discuss your findings and specify the loads at which the voltage drops below 0.9 p.u.; [5  marks]

•    Note:

o To change the setting of reactive power for the load, go into the power flow’ tab in the load model;

Question 1.3: Network conditions with loads at 0.9 inductive power factor with reactive power compensation [20 marks]

•    One approach to keep the load voltage as close to 1.0 p.u. as possible is to connect a source of reactive power near the load bus. In this case, a shunt capacitor or a shunt inductor is added to the load bus. It will produce or absorb reactive power to support and maintain the voltage.

•    Connect a shunt capacitor/inductor model to the load bus and change its rated voltage and adjust the rated reactive power setting. Repeat the calculations in Question 1.2.

•    Find the most suitable values of the reactive power generation/absorption of the shunt capacitor/inductor to maintain the load bus voltage as close as possible to 1.0 p.u. for each load level. And record the reactive power values, new active and reactive powers as well as voltage magnitudes and phases of the generator bus and load bus. Present your recordings in the form. of table/figure in your report;  [15  marks]

•    Discuss your findings;                                                                                       [5 marks]

•    Note:

o To set the reactive power rating, goto the shunt RLC ’ model, choose capacitor or inductor type, and adjust the rated reactive power value

o Keep the number of step in the ‘shunt capacitor’ as 1.

4.  Problem 2 _ N-R Iterative Power Flow Calculation [50 marks]

Preparation

Open the project file ‘Power System Analysis_Lab  1_P2.pfd’. Ensure the library contains generator type G1.

Problem formation:

The three-bus system is given in Figure Q2. System voltage level is 400 kV. Voltages and line impedances are in per unit. The chosen system power base is 100 MVA.

Figure Q2

For transmission line, create a ‘line type’ for all three lines. For the ‘line type’:

•    Rated voltage: 400 kV

•    Rated current: 2 kA

•    Type: overheadline

•    1,2- Sequence reactance X’: 10 Ohm/km

•   Note: you need to go back to the line model to change the length of line to match the given impedance value in p.u.

For generator, select the provided generator type ‘G1’ in the library. However, change the generator ratings in the type to:

•    Rated apparent power: 200 MVA

•    Rated voltage: 400 kV

•    Rated power factor: 1.0

Question 2.1: Load Flow Result by Simulation [10 marks]

•    Run the power flow calculation

•    Record the solutions of active and reactive power flows on each branch as well as voltage magnitudes and phases of the buses. Analyse the results and present your  recordings in the form. of table in your report;   [10 marks]

Question 2.2: Verification of Simulation result by Hand Calculation using Newton-Raphson Approach [40 marks]

•    Write the bus admittance bus for this system                                 [5 marks]

•    Formulate the Newton-Raphson problem and formulate the Jacobian matrix with unknown quantities                           [5 marks]

•    With initial guess of θ2  = θ3  = 0°, |v3| =  1, find the values of Jacobian matrix elements and write the Jacobian matrix J0                      [5 marks]

•    Find the unknown quantities in the 1st  iteration, and compare with the exact results from the simulation                    [10 marks]

•    Continue to the 2nd  iteration, finding the updated Jacobian matrix J1  and calculate the unknown quantities in the 2nd  iteration, and compare with the exact results from the simulation and provide your remarks.                      [15 marks]


站长地图